XM31-915-HP - 10040317
Power Supply
Alarms
Battery
Log In...
English
Español
Français
Português
Deutsch
Overview
Hardware
Power Supply
Batteries
Environmental I/O
Components
Network
Ethernet
Advanced
Interfaces
Network Services
Management
System Data
SNMP
Alarms
Utility Power
History
Power Supply Events
Power Supply Configuration
Battery Events
Standby Events
Alarm Log
d
Power Supply
Model
ALPHA/XM31-915-HP
Firmware
V2.06.0
Major Alarm
OK
Minor Alarm
OK
Operational Mode
Line
Charger Mode
Float
Tamper
Door closed
Power Supply Language
English
Power Supply Priority
Normal
d
Input
AC Line Mode
OK
Voltage
121.36
V
Current
6.21
A
Power
658
W
Frequency
60
Hz
Tap Status
Normal
Frequency Range
3.00
Hz
Current Limit
17.00
A
Input Power Consumption
11,173
Wh
1
Output
Voltage
86.84
V
Power
532
W
Apparent Power
571.40
VA
Frequency
60.02
Hz
Percent Load
43.80
%
Output Setting
90 V
Output Regulation
Coarse override
Over-current Tolerance
3.000
sec
Retry Delay
60
sec
Retry Limit
20
Active Drop Alarm
OK
Active Drop Threshold
50
W
Current
6.58
A
d
Inverter
Inverter Status
Off
End of Discharge Type
String
End of Discharge Level
1.75
V/cell
Reduced Peak Mode
Enable
Total Standby Events
25
Time Since Last Standby Event
8d 10h:59m
Time in Last Standby Event
0d 0h:01m
Total Time in Standby
206
min
Standby Events Since Reset
6
Time in Standby Since Reset
1
min
Time Since Reset
205
day(s)
Total Run Time
205
day(s)
Transformer Run Time
205
day(s)
Total Downtime
0d 0h:00m
Oil Cap Lifespan Consumed
4.6
%
d
Self Test
Deep Discharge Cycle
Timed
Test Countdown
11
day(s)
Test Duration
10
min
Test Interval
30
day(s)
Test Inhibit
No
→ CSV
→ Excel
Copyright © 2017-2023 EnerSys. All Rights Reserved.
www.alpha.com
|
www.enersys.com
Close